380070
PROFIBUS/PROFINET: No input slot available for basic address %1 (length %2)
Parameters:
%1 = Logical base address of the requested area
%2 = Size of the area in bytes
Explanation:
An incorrect logical base address was specified for a digital or analog input. Either no slot has been configured for this
base address or the requested area extends beyond the end of the slot.
Length=1 indicates a digital input.
Length=2 indicates a analog input.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Enter correct base addresses in the machine data:
- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTIN.
- For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTIN.
- NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system
manufacturer.
Programm
continuation:
Switch control OFF - ON.
380071
PROFIBUS/PROFINET: No output slot available for basic address %1 (size %2)
Parameters:
%1 = Logical base address of the requested area
%2 = Size of the area in bytes
Explanation:
An incorrect logical base address was specified for a digital or analog input. Either no slot has been configured for this
base address or the requested area extends beyond the end of the slot.
For length =1 it is a digital output,
For length =2 it is an analog output.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Enter correct base addresses in the machine data:
- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
- For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
- NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system
manufacturer.
Programm
continuation:
Switch control OFF - ON.
380072
PROFIBUS/PROFINET: Output slot for basic address %1 (size %2) not allowed
Parameters:
%1 = Logical base address of the requested area
%2 = Size of the area in bytes
Explanation:
An incorrect logical base address was set for a digital or analog output, the area is resides in the access range of the PLC
(PIQ, base addresses < 256).
For length =1 it is a digital output,
For length =2 it is an analog output.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
SINUMERIK 808D ADVANCED alarms
5.4 Drive alarms
Diagnostics Manual
518
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2
Содержание SINUMERIK 808D
Страница 528: ...SINUMERIK 808D ADVANCED alarms 5 6 PLC user alarms Diagnostics Manual 528 Diagnostics Manual 06 2015 6FC5398 6DP10 0BA2 ...
Страница 534: ...System responses 6 2 Cancel criteria for alarms Diagnostics Manual 534 Diagnostics Manual 06 2015 6FC5398 6DP10 0BA2 ...
Страница 560: ...Data backup 8 2 External data backup Diagnostics Manual 560 Diagnostics Manual 06 2015 6FC5398 6DP10 0BA2 ...
Страница 566: ...Appendix A Diagnostics Manual 566 Diagnostics Manual 06 2015 6FC5398 6DP10 0BA2 ...