Electrical installation
4.10 Other connections
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
127
4.10.6
Cabinet illumination with service socket (option L50)
Description
With option L50, cabinet lighting and an additional service socket outlet is included for
grounding plug (connector type F) according to CEE 7/4. The power supply for the cabinet
lighting and the service socket is external and must be fuse-protected for max. 10 A.
The cabinet lighting consists of an LED hand lamp with On/Off switch and with magnetic
fasteners on an approx. 3 m long connecting cable. In the as-delivered condition, the
flashlight is already positioned at the defined marks in the cabinet door and the connecting
cable is wound on the holder.
Note
During operation of the cabinet unit, the cabinet lighting must remain attached in its position
on the cabinet door. The position on the cabinet door is marked by an adhesive label. The
connecting cable must be wound on its holder.
Connection
Table 4- 29 Terminal block X390 – connection for cabinet lighting with service socket
Terminal
Designation
Technical data
1
L1
230 V AC
power supply
2
N
3
PE
Protective conductor
Max. connectable cross-section: 4 mm
2
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......