Electrical installation
4.10 Other connections
Converter cabinet units
128
Operating Instructions, 07/2016, A5E03347396A
4.10.7
Cabinet anti-condensation heating (option L55)
Description
The anti-condensation heating is used at low ambient temperatures and high levels of
humidity to prevent condensation forming.
One 100 W heater is installed for a 400 mm and 600 mm cabinet panel, and two 100 W
heaters for an 800/1000 and 1200 mm cabinet panel. The power supply (110 to 230 V AC)
must be provided externally and protected with a fuse of up to 16 A.
WARNING
Danger to life due to dangerous electrical voltage from an external auxiliary supply
When the external supply voltage for the cabinet anti-condensation heating is connected,
dangerous voltages are present in the cabinet unit even when the main switch is open.
Death or serious injury can result when live parts are touched.
•
Observe the general safety rules when working on the device.
CAUTION
Danger of injury through contact with hot surfaces on the cabinet anti-condensation heating
In operation, the cabinet anti-condensation heating can reach high temperatures, which can
cause burns if touched.
•
Allow the cabinet anti-condensation heating to cool down before starting any work.
•
Use the appropriate personnel protection equipment, e.g. gloves.
Note
Provide a temperature controlled supply voltage
The supply voltage can be provided using a temperature control to avoid unnecessarily
operating the anti-condensation heating for higher ambient temperatures.
Connecting
Table 4- 30 Terminal block X240 – connection for cabinet anti-condensation heating
Terminal
Designation
Technical data
1
L1
110 to 230 V AC
Power supply
2
N
3
PE
Protective conductor
Max. connectable cross-section: 4 mm
2
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......