Electrical installation
4.10 Other connections
Converter cabinet units
186
Operating Instructions, 07/2016, A5E03347396A
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved through one of the following measures:
1.
Also route the reference ground of the digital inputs.
2.
A jumper to terminal M. (Note: This removes the electrical isolation for these digital
inputs.)
Note
If the 24 V supply is briefly interrupted, then the digital outputs are deactivated during this
time.
X127: LAN (Ethernet)
Table 4- 64 X127 LAN (Ethernet)
Pin
Designation
Technical data
1
TXP
Ethernet transmit data +
2
TXN
Ethernet transmit data -
3
RXP
Ethernet receive data +
4
Reserved, do not use
5
Reserved, do not use
6
RXN
Ethernet receive data -
7
Reserved, do not use
8
Reserved, do not use
Connector type: RJ45 socket
Note
The LAN (Ethernet) interface does not support Auto MDI(X). For this reason, only crossover
cables may be used to connect devices.