Operation
6.3 Basic information about the drive system
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
275
6.3.5
Propagation of faults
Forwarding faults to the Control Unit
In the case of faults that are, for example, triggered by the Control Unit or a Terminal
Module, central functions of the drive are also often affected. As a result of propagation,
faults that are triggered by one drive object are therefore forwarded to other drive objects.
This behavior also applies to the faults that are set in a DCC chart on the Control Unit with
the aid of the DCC block.
Propagation types
There are the following types of propagation:
●
BICO
The fault is propagated to all active drive objects with closed-loop control functions
(infeed, drive) to which there is a BICO interconnection.
●
DRIVE
The fault is propagated to all active drive objects with closed-loop control functions.
●
GLOBAL
The fault is propagated to all active drive objects.
●
LOCAL
The behavior of this propagation type is dependent on parameter p3116.
–
With binector input p3116 = 0 (factory setting) the following applies:
The fault is propagated to the first active drive object with closed-loop control
functions.
–
With binector input p3116 = 1 signal, the following applies:
The fault is not forwarded.
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......