Parameter macro p0015 = G150 cabinet unit
This macro is used to make default settings for operating the cabinet unit.
Table A- 1
Parameter macro p0015 = G150 cabinet unit
Sink
Source
Parameters
Description
DO
Parameters
Description
DO
p0400[0]
Encoder type selection
Vector
9999
User-defined
Vector
p0404[0]
Encoder configuration
Vector
200008h
Vector
p0405[0]
Square-wave encoder track A/B
Vector
9h
Bipolar, like A/B track
Vector
p0408[0]
Rotary encoder pulse no.
Vector
1024
1024 pulses per revolution
Vector
p0420[0]
Encoder connection
Vector
0x2
Encoder connection = terminal
Vector
p0500
Technology application
Vector
1
Pumps, fans
Vector
p0600
Motor temperature sensor for moni-
toring
Vector
0
No sensor
Vector
p0601
Motor temperature sensor type
Vector
0
No sensor
Vector
p0603
CI: Motor temperature
Vector
r4105
Sensor on TM31
TM31
p0604
Motor overtemperature alarm
threshold
Vector
120
120 °C
Vector
p0605
Motor overtemperature fault thresh-
old
Vector
155
155 °C
Vector
p0606
Motor overtemperature timer
Vector
0
0 s
Vector
p0610
Response to motor overtemperature
condition
Vector
12
Messages, no reduction of
I_max, temperature saved
Vector
p0700[0]
Macro binector input (BI)
Vector
70005
PROFIdrive
Vector
p0864
BI: Infeed operation
Vector
1
Vector
p1000[0]
Macro connector inputs (CI) for
speed setpoints
Vector
100001
PROFIdrive
Vector
p1001
CO: Fixed speed setpoint 1
Vector
300
300 rpm
Vector
p1002
CO: Fixed speed setpoint 2
Vector
600
600 rpm
Vector
p1003
CO: Fixed speed setpoint 3
Vector
1500
1500 rpm
Vector
p1083
CO: Speed limit in positive direction
of rotation
Vector
6000
6000 rpm
Vector
p1086
CO: Speed limit in negative direc-
tion of rotation
Vector
-6000
-6000 rpm
Vector
p1115
Ramp-function generator selection Vector
1
Extended ramp-function genera-
tor
Vector
p1120
Ramp-function generator ramp-up
time
Vector
20
20 s
Vector
p1121
Ramp-function generator ramp-
down time
Vector
30
30 s
Vector
p1135
OFF3 ramp-down time
Vector
10
10 s
Vector
p1200
Flying restart operating mode
Vector
0
Flying restart not active
Vector
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......