Operation
6.9 Communication via PROFINET IO
Converter cabinet units
358
Operating Instructions, 07/2016, A5E03347396A
PROFINET IO with RT (Real Time)
Real-time data is treated with a higher priority than TCP(UDP)/IP data. Transmission of time-
critical data takes place at guaranteed time intervals. RT communication is the basis for data
exchange with PROFINET IO.
PROFINET IO with IRT (Isochronous Real Time)
Isochronous real time: Real time property of PROFINET IO where IRT telegrams are
transferred deterministically via planned communication paths in a defined sequence to
achieve the best possible synchronism and performance between the IO controller and IO
device (drive unit). IRT is also known as time-scheduled communication whereby knowledge
about the network structure (topology) is utilized. IRT requires special network components
that support planned data transfer.
SINAMICS cycle times of minimum 250
μs (on
-board) / 500
μs (CBE20) and a jitter accuracy
of less than 1
μs can be achieved when this transmission method is implemented.
Figure 6-42 Bandwidth distribution/reservation, PROFINET IO
6.9.2.3
Addresses
MAC address
Every Ethernet and PROFINET interface is assigned a worldwide unique device identifier in
the factory. This 6-byte long device identifier is the MAC address. The MAC address is
divided up as follows:
●
3 bytes for the manufacturer's ID
●
3 bytes device identifier (consecutive number).
The MAC address is printed on a label (CBE20) or specified on the rating plate (CU320-2
PN), e.g.: 08-00-06-6B-80-C0.
The Control Unit CU320-2 PN has two onboard interfaces:
●
One Ethernet interface
●
A PROFINET interface with two ports
The two MAC addresses of the Ethernet and PROFINET interfaces are stamped on the
rating plate.
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......