![Siemens SINAMICS G150 Скачать руководство пользователя страница 656](http://html.mh-extra.com/html/siemens/sinamics-g150/sinamics-g150_operating-instructions-manual_378202656.webp)
Technical specifications
12.3 Technical data
Converter cabinet units
656
Operating Instructions, 07/2016, A5E03347396A
Article number
6SL3710- 2GH42-4EA3
2GH42-7EA3
Short-circuit current rating per IEC
6)
kA
2 x 85
2 x 85
Minimum short-circuit current
7)
A
2 x 2500
2 x 3000
1)
Rated output of a typical 6-pole standard induction motor based on I
L
or I
H
at 690 V 3 AC 50 Hz.
2)
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
3)
The base-load current I
H
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
4)
The current values given here are based on the rated output current.
5)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
(National Electrical Code) or CEC (Canadian Electrical Code) standards.
6)
In conjunction with the specified fuses or circuit breakers.
7)
Minimum current required for reliably triggering protective devices.
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......