Setpoint channel and closed-loop control
7.3 V/f control
Converter cabinet units
430
Operating Instructions, 07/2016, A5E03347396A
Parameter
value
Meaning
Application / property
5
Precise frequency
drives (textiles)
Characteristic (see parameter value 0) that takes into account the specific technolog-
ical features of an application (e.g. textile applications).
•
The current limitation (Imax controller) only affects the output voltage and not the
output frequency.
•
The slip compensation and resonance damping are disabled.
6
Precise frequency
drives with flux cur-
rent control (FCC)
Characteristic (see parameter value 1) that takes into account the specific technolog-
ical features of an application (e.g. textile applications).
•
The current limitation (Imax controller) only affects the output voltage and not the
output frequency.
•
The slip compensation and resonance damping are disabled.
Voltage losses in the stator resistance for static / dynamic loads are also compen-
sated (flux current control, FCC). This is particularly useful for small motors, since
they have a relatively high stator resistance.
7
Parabolic character-
istic and ECO
Characteristic (see parameter value 1) and Eco mode at constant operating point.
•
At constant operating point, the efficiency is optimized by varying the voltage.
•
Active slip compensation is necessary here; the scaling must be set so that the
slip is fully compensated (p1335 = 100%).
19
Independent voltage
setpoint
The user can define the output voltage of the Power Module independently of the
frequency using BICO parameter p1330 via the interfaces (e.g., analog input AI0 of
the TM31 –> p1330 = r4055[0]).
Function diagram
FP 6301
V/f characteristic and voltage boost
Parameter
•
p1300
Open-loop/closed-loop control operating mode
•
p1320
V/f control programmable characteristic frequency 1
...
•
p1327
V/f control programmable characteristic voltage 4
•
p1330
CI: V/f control independent of voltage setpoint
•
p1331
Voltage limitation
•
p1333
V/f control FCC starting frequency
•
r1348
V/f control Eco factor actual value
•
p1350
V/f control soft starting
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......