Operation
6.6 Control via the operator panel
Converter cabinet units
304
Operating Instructions, 07/2016, A5E03347396A
Scaling to motor current
In this menu, the reference variable for the bar-type display of parameter r0027 (absolute
actual current value smoothed) can be changed over in the operating screen forms.
Scaling to motor current (factory setting: No)
●
Yes: The bar-type display of parameter r0027 in the operating screen form is displayed
based on parameter p0305 (rated motor current).
●
No: The bar-type display of parameter r0027in the operating screen form is displayed
based on parameter p2002 (reference current).
Reset AOP settings
When you choose this menu option, the AOP factory settings for the following are restored:
●
Language
●
Display (brightness, contrast)
●
Operating screen
●
Control settings
Note
Restoring the factory setting
When you reset parameters, all settings that are different to the factory settings are reset
immediately. This may cause the cabinet unit to switch to a different, unwanted operational
status.
For this reason, you should always take great care when resetting parameters.
6.6.5.5
AOP diagnostics
Software/database version
You can use this menu to display the firmware and database versions.
The database version must be compatible with the drive software status (you can check this
in parameter r0018).
Database contents
For service purposes, the contents of the database are displayed in the screen form.
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......