Table 4-8
Maximum permissible motor cable lengths for FSD … FSF
1)
Inverter frame
size
EMC category: Second en‐
vironment, C2 or C3
No EMC category
Inverter with filter
Inverter with or without fil‐
ter, without output reactor
Inverter without filter, with
two output reactors in ser‐
ies
with shielded motor cable
Shielded
Unshielded
Shielded
Unshielded
FSD, FSE
2)
150 m
200 m
300 m
350 m
525 m
FSF
2)
150 m
300 m
450 m
525 m
800 m
1)
The values are valid for a pulse frequency set at the factory
2)
The specified motor cable lengths apply for a line voltage of 400 V