![Siemens SINAMICS G120C Скачать руководство пользователя страница 427](http://html.mh-extra.com/html/siemens/sinamics-g120c/sinamics-g120c_operating-instructions-manual_376473427.webp)
10.10.6
Braking resistor
Assigning the braking resistor to the inverter:
Dimensions and mounting dimensions:
Mounting base components (Page 47)
Mounting the braking resistor (Page 63)
Table 10-24 Technical data of the braking resistor
Article no.
6SE6400-4BD11-0AA0
6SL3201-0BE14-3AA0
6SL3201-0BE21-0AA0
Resistance
390 Ω
370 Ω
140 Ω
Pulse power P
max
2.0 kW
1.5 kW
4 kW
Rated power P
DB
100 W
75 W
200 W
Temperature contact (NC
contact)
250 VAC / 2.5 A
250 VAC / 2.5 A
250 VAC / 2.5 A
Degree of protection
IP20
IP20
IP20
Weight
1.0 kg
1.5 kg
1.8 kg
Table 10-25 Technical data of the braking resistors
Article no.
6SL3201-0BE21-8AA0
6SL3201-0BE23-8AA0
JJY:023422620001
Resistance
75 Ω
30 Ω
25 Ω
Pulse power P
max
7.5 kW
18.5 kW
22 kW
Rated power P
DB
375 W
925 W
1100 W
Temperature contact (NC
contact)
250 VAC / 2.5 A
250 VAC / 2.5 A
250 VAC / 2.5 A
Degree of protection
IP20
IP20
IP21
Weight
2.7 kg
6.2 kg
7.0 kg
Table 10-26 Technical data of the braking resistors
Article no.
JJY:023424020001
JJY:023434020001
JJY:023454020001
Resistance
15 Ω
10 Ω
7.1 Ω
Pulse power P
max
37 kW
55 kW
77 kW
Rated power P
DB
1850 W
2750 W
3850 W
Temperature contact (NC
contact)
250 VAC / 2.5 A
250 VAC / 2.5 A
250 VAC / 2.5 A
Degree of protection
IP21
IP21
IP21
Weight
9.5 kg
13.5 kg
20.5 kg
Technical data
10.10 Accessories
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF