Number
Cause
Remedy
A50001
PROFINET configuration error
A PROFINET control is attempting to establish a connection with a faulty
configuration telegram. Check whether "Shared Device" is activated (p8929
= 2).
A50010
PROFINET name of station inva‐
lid
Correct the name of station (p8920) and activate (p8925 = 2).
A50020
PROFINET: Second control
missing
"Shared Device" is activated (p8929 = 2). However, only the connection to a
PROFINET control is present.
For further information, please refer to the List Manual.
Overview of the manuals (Page 459)
Alarms, faults and system messages
8.5 List of alarms and faults
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
367