6.17.6
Ramp-function generator
The ramp-function generator in the setpoint channel limits the rate change of the speed setpoint
(acceleration). A reduced acceleration reduces the accelerating torque of the motor. As a
consequence, the motor reduces the stress on the mechanical system of the driven machine.
The extended ramp-function generator not only limits the acceleration, but by rounding the
setpoint, also acceleration changes (jerk). This means that the motor does not suddenly
generate a torque.
Extended ramp-function generator
The ramp-up and ramp-down times of the extended ramp-function generator can be set
independently of each other. The optimum times that you select depend on your particular
application in question and can range from just a few 100 ms (e.g. for belt conveyor drives) to
several minutes (e.g. for centrifuges).
5DPSXSWLPH
5DPS
GRZQWLPH
(IIHFWLYHUDPSXS
WLPH
(IIHFWLYHUDPSGRZQ
WLPH
0D[LPXP
VSHHG
\
W
[
[
\
W
[
\
[
\
W
\
\
[
[
[
[
Initial and final rounding permit smooth, jerk-free acceleration and braking.
The ramp-up and ramp-down times of the motor are increased by the rounding times:
● Effective ramp-up time = p1120 + 0.5 × (p1130 + p1131).
● Effective ramp-down time = p1121 + 0.5 × (p1130 + p1131).
Table 6-44
Additional parameters to set the extended ramp-function generator
Parameter
Description
p1120
Ramp-function generator, ramp-up time (factory setting: 10 s)
Accelerating time in seconds from zero speed up to the maximum speed p1082
p1121
Ramp-function generator, ramp-down time (factory setting: 10 s)
Braking time in seconds from the maximum speed down to standstill
Advanced commissioning
6.17 Setpoint calculation
SINAMICS G120C converter
248
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF