6.28
Kinetic buffering (Vdc min control)
Kinetic buffering increases the drive availability. The kinetic buffering utilizes the kinetic energy
of the load to buffer line dips and failures. During a line dip, the inverter keeps the motor in the
switched-on state for as long as possible. One second is a typical, maximum buffer time.
Preconditions
The following prerequisites must be fulfilled to practically use the "kinetic buffering" function:
● The driven load has a sufficiently high inertia.
● The application allows a motor to be braked during a power failure.
Function
When the line supply dips or is interrupted, the DC link voltage in the inverter decreases. At
an adjustable threshold, kinetic buffering intervenes (V
DC min
control). The V
DC min
control forces
the load to go into slightly regenerative operation. As a consequence, the inverter covers its
power loss and the losses in the motor with the kinetic energy of the load. The load speed
decreases; however, during kinetic buffering, the DC voltage remains constant. After the line
supply returns, the inverter immediately resumes normal operation.
'&OLQNYROWDJH
0RWRULQJ
*HQHUDWLQJ
2SHUDWLRQ
6SHHG
9
'&PLQ
FRQWUROOHULV
DFWLYH
3RZHUIDLOXUH
U
S
W
W
W
W
Figure 6-65 Principle mode of operation of kinetic buffering
Parameter
Description
r0056.15
Status word closed-loop control
0 signal
V
DC min
controller is not active
1 signal
V
DC min
controller is active (kinetic buffering)
p0210
Device supply voltage (factory setting: 400 V)
Advanced commissioning
6.28 Kinetic buffering (Vdc min control)
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
309