Parameter
Description
p1240
V
DC
controller configuration (factory setting: 1)
0
Inhibit V
DC
controller
1
Enable V
DC max
controller
2
Enable V
DC min
controller (kinetic buffering)
3
Enable V
DC min
controller and V
DC max
controller
p1245
V
DC min
controller activation level (kinetic buffering) (factory setting depends on the Power
Module, 73 % or 76 %)
r1246
V
DC min
controller activation level[V]
r1246 = p1245 × √2 × p0210
p1247
V
DC min
controller dynamic factor (factory setting: 300 %)
p1255
V
DC min
controller time threshold (factory setting: 0 s)
Maximum duration of the kinetic buffering If kinetic buffering lasts longer than that speci‐
fied in the parameter value, the inverter outputs fault F7406.
A value of 0 deactivates the monitoring.
p1257
V
DC min
controller speed threshold (factory setting: 50 rpm)
When fallen below, the inverter outputs fault F7405.
Advanced commissioning
6.28 Kinetic buffering (Vdc min control)
SINAMICS G120C converter
310
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF