Dead band
With the control enabled, electromagnetic interference on the signal cable can cause the motor
to slowly rotate in one direction in spite of a speed setpoint = 0.
'HDGEDQG
'HDGEDQG
9P$
9P$
The dead band acts on the zero crossover of
the analog input characteristic. Internally, the
inverter sets its speed setpoint = 0, even if
the signal at the analog input terminals is
slightly positive or negative. This prevents
the inverter from rotating the motor at a
speed setpoint = 0.
p0764[0]
Analog input dead band (factory setting: 0)
Using an analog input as digital input
An analog input can also be used as digital input.
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
169