High Overload and Low Overload (Page 403)
Set the supply voltage of the inverter.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
● INDUCT: Third-party induction motor
● 1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
● 1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
● 1PH8 IND: Induction motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
inverter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor
data from p0304 and higher from the rating plate.
87 Hz motor operation The BOP-2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
● SELF: Natural cooling
● FORCED: Forced-air cooling
● LIQUID: Liquid cooling
● NO FAN: Without fan
3
,1992/7
3
0277<3(
3
027&2'(
+=
3
02792/7
3
027&855
3
02732:
3
027)5(4
3
027530
3
027&22/
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
129
Содержание SINAMICS G120C
Страница 2: ......
Страница 14: ...Table of contents SINAMICS G120C converter 14 Operating Instructions 09 2017 FW V4 7 SP9 A5E34263257B AF ...
Страница 469: ......