6.4.4
Three-wire control, method 1
&ORFNZLVH
&RXQWHUFORFNZLVH
21
&RXQWHUFORFNZLVH
21
&ORFNZLVH
(QDEOH2))
6SHHGVHWSRLQW
W
W
W
W
6723
6723
6723
Figure 6-8
Three-wire control, method 1
The "Enable" command is a precondition for switching on the motor. Commands "ON clockwise
rotation" and "ON counter-clockwise rotation" switch on the motor - and simultaneously select
a direction of rotation. Removing the enable switches the motor off (OFF1).
Table 6-17
Function table
Enable / OFF1
ON clockwise rota‐
tion
ON counter-clock‐
wise rotation
Function
0
0 or 1
0 or 1
OFF1: The motor stops.
1
0→1
0
ON: Clockwise motor rotation.
1
0
0→1
ON: Counter-clockwise motor rota‐
tion.
1
1
1
OFF1: The motor stops.
Table 6-18
Select three-wire control, method 1
Parameter
Description
p0015 = 19
Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI 0: Enable / OFF1
DI 1: ON clockwise rotation
DI 2: ON counter-clockwise rotation
Table 6-19
Changing the assignment of the digital inputs
Parameter
Description
p3330[0 … n] = 722.x
BI: 2/3 wire control command 1 (enable/OFF1)
p3331[0 … n] = 722.x
BI: 2/3 wire control command 2 (ON clockwise rotation)
p3332[0 … n] = 722.x
BI: 2/3 wire control command 3 (ON counter-clockwise rotation)
Example: p3332 = 722.0 ⇒ DI 0: ON counter-clockwise rotation
Advanced commissioning
6.4 Controlling clockwise and counter-clockwise operation via digital inputs
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
177