10.5
Technical data dependent on the power
Feature
Data
FSAA … FSC
FSD … FSF
Required line impe‐
dance U
K
1 % ≤ U
K
< 4 %
For U
K
< 1 %, we recommend a line reactor or an
inverter with the next higher power rating.
U
K
< 4 %
A line reactor is not required.
Power factor λ
0.7 without line reactor for U
K
≥ 1 %
0.85 with line reactor for U
K
< 1 %
> 0.9
Pulse frequency
Factory setting: 4 kHz
Factory setting:
4 kHz for inverters with an LO base load power
< 75 kW
2 kHz for inverters with an LO base load power
≥ 75 kW
Change in 2‑kHz steps:
2 kHz … 16 kHz
Change in 2‑kHz steps:
2 kHz … 16 kHz for inverters with an LO base load
power < 55 kW
2 kHz … 8 kHz for inverters with an LO base load
power = 55 kW … 90 kW
2 kHz … 4 kHz for inverters with an LO base load
power ≥ 110 kW
If you increase the pulse frequency above the factory setting then the inverter reduces the maximum
output current.
Permissible ambi‐
ent temperature
The permissible ambient temperature depends on the following conditions:
● Frame size (FS) of the inverter
● Inverter fieldbus interface
● Operator panel
:LWKRSHUDWRUSDQHO
)6$)6&
)6$$
)6$)6&
)6')6)
3HUPLVVLEOHDPELHQWWHPSHUDWXUHZLWKRXWUHGXFLQJWKHRXWSXWFXUUHQW
)LHOGEXV
3HUPLVVLEOHDPELHQWWHPSHUDWXUHZKHQUHGXFLQJWKHRXWSXWFXUUHQW
3HUPLVVLEOHDPELHQWWHPSHUDWXUHZLWKWKHRSHUDWRUSDQHOLQVHUWHG
352),%86866
352),1(7(WKHU1HW,3
352),1(7
r& r&
r&
r&
r&
r&
r&
r&
r&
r&
Restrictions for special ambient conditions (Page 414)
Device-dependent technical data
The inverter input currents specified in the following are applicable for an input voltage of 400 V.
Technical data
10.5 Technical data dependent on the power
SINAMICS G120C converter
406
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF