![Siemens SINAMICS G120C Скачать руководство пользователя страница 285](http://html.mh-extra.com/html/siemens/sinamics-g120c/sinamics-g120c_operating-instructions-manual_376473285.webp)
6.20.1
DC braking
DC braking is used for applications where the motor must be actively stopped; however, neither
an inverter capable of energy recovery nor a braking resistor is available.
Typical applications for DC braking include:
● Centrifuges
● Saws
● Grinding machines
● Conveyor belts
DC braking is not permissible in applications involving suspended loads, e.g. lifting equipment/
cranes and vertical conveyors.
Function
NOTICE
Motor overheating as a result of DC braking
The motor will overheat if you use DC braking too frequently or use it for too long. This may
damage the motor.
● Monitor the motor temperature.
● Allow the motor to adequately cool down between braking operations.
● If necessary, select another motor braking method.
With DC braking, the inverter outputs an internal OFF2 command for the time that it takes to
de-energize the motor p0347 - and then impresses the braking current for the duration of the
DC braking.
The DC-braking function is possible only for induction motors.
4 different events initiate DC braking
DC braking when falling below a starting speed
'&EUDNLQJ
DFWLYH
2))
6WDUWVSHHG
7LPH
LQWHUYDO
Q
S
W
W
Requirement:
p1230 = 1 and p1231 = 14
Function:
1. The motor speed has exceeded the starting
speed.
2. The inverter activates the DC braking as
soon as the motor speed falls below the
starting speed.
Advanced commissioning
6.20 Electrically braking the motor
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF