Application class
Standard Drive Control
Dynamic Drive Control
Max. output fre‐
quency
550 Hz
240 Hz
Commissioning
● Unlike "Dynamic Drive Control," no speed
controller needs to be set
● In comparison to setting "EXPERT":
– Simplified commissioning using
predefined motor data
– Reduced number of parameters
● Standard Drive Control is preset for Power
Modules, frame size A … frame size C
● Fewer number of parameters when compared
to setting "EXPERT"
● Dynamic Drive Control is preset for Power
Modules, frame size D … frame size F
5.4.3
Standard Drive Control
Select the motor standard:
● KW 50HZ: IEC
● HP 60HZ: NEMA
● KW 60HZ: IEC 60 Hz
Set the inverter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
● INDUCT: Third-party induction motor
● 1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
● 1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
● 1PH8 IND: Induction motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
inverter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor
data from p0304 and higher from the rating plate.
87 Hz motor operation The BOP-2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
3
(8586$
3
,1992/7
3
0277<3(
3
027&2'(
+=
3
02792/7
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120C converter
124
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF