Procedure, FSF:
Proceed as follows to mount the EMC connecting bracket and the shield plate:
1. If you are using an inverter with an integrated line filter, then mount the EMC connecting
bracket on the shield plate
①
.
On inverters without a filter, the EMC connecting bracket is not included in the scope of
supply of the inverter.
2. Screw the shield module to the inverter
②
using three screws, as shown in the figure.
1P
1P
You have mounted the EMC connecting bracket and the shield plate.
Mounting on a control cabinet panel
Table 4-3
Drilling patterns and mounting equipment, FSAA … FSC
Frame size AA
0.55 kW … 2.2 kW
Frame size A
3.0 kW … 4.0 kW
Frame size B
5.5 kW … 7.5 kW
Frame size C
11 kW … 18.5 kW
Drilling pattern
Drilling pattern with‐
out shield plate
When the shield
plate is mounted,
the drilling pattern
is compatible to
frame size A
Mounting parts 2 × M4 bolts
2 × M4 nuts
2 × M4 washers
3 × M4 bolts
3 × M4 nuts
3 × M4 washers
4 × M4 bolts
4 × M4 nuts
4 × M4 washers
4 x M5 bolts
4 x M5 nuts
4 x M5 washers
Locked-rotor
(starting) torque
2.5 Nm
2.5 Nm
2.5 Nm
2.5 Nm
Installing
4.3 Installing the inverter
SINAMICS G120C converter
54
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF