6.3.3
Analog input
Overview
S>@
U
&,S\\\\
$,
$,
,
8
The parameter p0756[x] and the switch on
the inverter specify the analog input type.
You define the analog input function by interconnecting parameter p0755[x] with a connector
input CI of your choice.
Interconnecting signals in the converter (Page 447)
Define the analog input type
The inverter offers a series of default settings, which you can select using parameter p0756[0]:
AI 0
Unipolar voltage input
0 V … +10 V
p0756[0] =
0
Unipolar voltage input monitored
+2 V … +10 V
1
Unipolar current input
0 mA … +20 mA
2
Unipolar current input monitored
+4 mA … +20 mA
3
Bipolar voltage input
‑10 V … +10 V
4
No sensor connected
---
8
In addition, you must also set the switch associated with the analog input. You can find the
switch on the Control Unit behind the front doors.
● Voltage input: Switch position U (factory setting)
● Current input: Switch position I
,
8
$,
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
SINAMICS G120C converter
166
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF