Properties of the SINAUT components
1.3 Properties of the TIM modules
SINAUT ST7 station control system
36
System Manual, 09/2016, C79000-G8976-C178-10
This is a combined RS-232/RS-485 port. As default, the ports are set to RS-232. The
switchover to RS-485 is set in the SINAUT configuration in NetPro and is therefore part of
the configuration data of the TIM 4R-IE.
Table 1- 9
Pinout of the connector of the combined RS-232/RS-485 port
Illustration
Pin no.
Signal name
Signal direction Remark
1
DCD
Input
2
RXD
Input
Switching over to RS-485
in the configuration
3
TXD
Output
Switching over to RS-485
in the configuration
4
DTR
Output
5
GND
6
-
7
RTS
Output
8
CTS
Input
9
-
Ethernet ports
The two Ethernet ports are designed as 8-pin RJ-45 Western jacks. The pinout is shown in
the following table.
Table 1- 10 Pinout of the RJ-45 Western jack for the Ethernet port
Illustration
Pin no.
Signal name
Signal direction
Remark
1
TXD+
Output
2
TXD-
Output
3
RXD+
Input
4
-
5
-
6
RXD-
Input
7
-
8
-
1.3.3.7
Standard connecting cables for the TIM 4R-IE
A modem or other transmission device can be connected to the 9-pin connector of the RS-
232/RS-485 port. The following standard connecting cables are available for connection to
these connectors.