Properties of the SINAUT components
1.3 Properties of the TIM modules
SINAUT ST7 station control system
18
System Manual, 09/2016, C79000-G8976-C178-10
TIM 3V-IE / TIM 3V-IE Advanced
The TIM 3V-IE is a SINAUT communications module for the SIMATIC S7-300. It has an RS-
232 interface to which a suitable modem can be connected. It also has an RJ-45 interface
that allows SINAUT communication over IP-based networks (LAN or WAN).
The TIM 3V-IE is available in a standard and advanced version:
●
TIM 3V-IE
With the TIM 3V-IE either the Ethernet interface or the RS-232 interface can be used for
the SINAUT communication.
●
TIM 3V-IE Advanced
With the TIM 3V-IE Advanced, the two interfaces can be used at the same time for
SINAUT communication. The two transmission paths can be completely independent of
each other or form a redundant transmission path.
Note
Low cycle monitoring time of the CPU
If the cycle monitoring time of the CPU is set to very low values, for example 1 ms, this can
lead to malfunctions on the TIM 3V-xxx. In this case, increase the cycle monitoring time of
the CPU or use a TIM 4R-xxx.
TIM 4R-IE
The TIM 4R-IE is suitable for installation in a SIMATIC S7-300 as a communications module
and can also be connected over Ethernet to one or more SIMATIC S7-400s and to ST7cc or
ST7sc PC control centers as a standalone device.
It has two combined RS-232/RS-485 interfaces to which a classic WAN (dedicated line or
dial-up network) can be connected via a suitable modem. It also has two RJ-45 interfaces
that allow SINAUT communication over Ethernet-based networks (LAN or WAN).
All four interfaces can be used at the same time for SINAUT communication. The four
transmission paths can all be different and operated independently. The two pairs of
interfaces can also form a redundant transmission path.
TIM 4
The TIM 4 is suitable for installation in the SIMATIC S7-300 as a communications module
and can also be connected via their MPI ports to one or more SIMATIC S7-300/-400s and to
ST7cc or ST7sc PC control centers as a standalone device.
It has two WAN connectors in the form of RS-232/RS-485 ports to which a suitable external
modem can be connected.
The two WANs that can be connected to a TIM 4 may be of the same type or different, for
example dedicated line plus telephone network. The two transmission paths can be either
completely independent of each other or form a redundant transmission path.
The TIM 4RD is equipped with a DCF77 radio clock receiver.
Содержание SIMATIC NET TeleControl SINAUT ST7
Страница 10: ...Preface SINAUT ST7 station control system 10 System Manual 09 2016 C79000 G8976 C178 10 ...
Страница 274: ...References 8 SINAUT ST7 station control system 274 System Manual 09 2016 C79000 G8976 C178 10 ...
Страница 292: ...Glossary SINAUT ST7 station control system 292 System Manual 09 2016 C79000 G8976 C178 10 ...