DISPLAY MODULE AND OFFICE CONFIGURATION EDITOR
_________________________________________________________________________________________________________
3-11
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
remain off for the configured Lamp Test Delay time, and then the lamps flash for the configured
Lamp Test On time, then they go off and the test is complete.
Option 7: Perform a repeat. When this is selected the user can edit the values for Lamp Test On
(default 15s), and Lamp Test Delay (default 30s). When the test is started, the lamps remain off
for the configured Lamp Test Delay time, and then the lamps flash for the configured Lamp Test
On time, then they go off for the Lamp Test Delay, then flash again for the Lamp Test On Time,
then go off, and then the test is complete.
3.1.2.3 IO & Logic View Screen
The IO & Logic View screen provides users with the status of all IO and logic conditions set in
the system as shown in Figure 3-14
Figure 3-14 IO & Logic View Screen
3.1.2.3.1
Logical View
The Logical View screen allows the user to see the status of the states used in the logic as
shown in Figure 3-15.
NOTE
Green indicates energized
Grey indicates de-energized
White indicates not used
Red indicates unhealthy