DETAILED CASE AND MODULE DESCRIPTION
_________________________________________________________________________________________________________
8-14
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
Diag Display /
Description
Cause
Remedy
DFT
Default Values set
(DIAG3001)
/
Operating
parameters have
been set to default.
New MCF has been loaded
Set the operating parameters to the required
values
DFT
Vital Cfg Parms set
to default
(DIAG3002)
/ Vital
Cfg parameters have
been set to default.
New MCF has been loaded or UCN
changed
Set the Vital Cfg parameters to the required
values
DFT
Configuration set to
default (DIAG3017)
/
Configuration set to
default.
The configuration parameters have
been set back to default due to
either:
•
MCF change
•
Template change
•
User setting default
Wait. The error will clear itself.
INIT
No VLP Comms
(DIAG3020)
/ The
VLP/CP LED on the
CPU card does not
light
The VLP is rebooting or is in its
Initial State and performing its initial
checks. This may occur after a VLP
reset, or after changing templates.
Wait for a minute for the VLP to power up. If
the VLP does not power up, check to see if it
is continuously rebooting by checking the
VLP Health LED.
MCF
MCF Checks failed
(DIAG3005)
/
Verification of MCF
data failed.
The MCF is invalid.
Obtain and load a valid MCF.
MCF
MCF Compatibility
incorrect
(DIAG3013)
/ MCF
and MEF are
incompatible
The installed MCF is incompatible
with the MEF software
Obtain compatible MCF or MEF software
MOD
Module Type Error
(DIAG3006)
/ The
MEF software is
incompatible with the
module hardware.
The MEF is incompatible with this
hardware.
Reload a valid MEF for this hardware.