7SR224 Argus Description of Operation
4.5
Quick Logic
The ‘Quick Logic’ feature allows the user to input up to 16 logic equations (E1 to E16) in text format. Equations
can be entered using Reydisp or at the relay fascia.
Each logic equation is built up from text representing control characters. Each can be up to 20 characters long.
Allowable characters are:
0, 1, 2, 3, 4, 5, 6, 7, 8, 9
Digit
( )
Parenthesis
!
‘NOT’
Function
.
‘AND’ Function
^
‘EXCLUSIVE OR’ Function
+
‘OR’
Function
En
Equation (number)
Fn
Function Key (number)
‘1’ = Key pressed, ‘0’ = Key not pressed
In
Binary Input (number)
‘1’ = Input energised, ‘0’ = Input de-energised
Ln
LED (number)
‘1’ = LED energised, ‘0’ = LED de-energised
On
Binary output (number)
‘1’ = Output energised, ‘0’ = Output de-energised
Vn
Virtual Input/Output (number)
‘1’ = Virtual I/O energised, ‘0’ = Virtual I/O de-energised
Example Showing Use of Nomenclature
E1= ((I1^F1).!O2)+L1
Equation 1 = ((Binary Input 1 XOR Function Key 1) AND NOT Binary Output 2)
OR
LED 1
When the equation is satisfied (=1) it is routed through a pick-up timer (
En Pickup Delay
), a drop-off timer (
En
Dropoff Delay
), and a counter which instantaneously picks up and increments towards its target (
En Counter
Target
).
The counter will either maintain its count value
En Counter Reset Mode
=
OFF
, or reset after a time delay:
En Counter Reset Mode
=
Single Shot
: The
En Counter Reset Time
is started only when the counter
is first incremented (i.e. counter value = 1) and not for subsequent counter operations. Where
En
Counter Reset Time
elapses and the count value has not reached its target the count value is reset to
zero.
En Counter Reset Mode
=
Multi Shot
: The
En Counter Reset Time
is started each time the counter is
incremented. Where
En Counter Reset Time
elapses without further count increments the count value
is reset to zero.
©2010 Siemens Protection Devices Limited
Chapter 1 Page 54 of 70