7SR224 Argus Description of Operation
3.7
Current Protection: Negative Phase Seq. OC (46NPS)
The negative sequence phase (NPS) component of current (I2) is derived from the three phase currents. It is a
measure of the quantity of unbalanced current in the system.
When the device is applied to reverse sequence networks, i.e. 1-3-2, the NPS/PPS sequence is corrected
automatically by the
Gn Phase
Rotation setting in the
CT/VT ConfigI menu.
Two NPS current elements are provided – 46IT and 46DT.
The 46IT element can be configured to be either definite time lag (DTL) or inverse definite minimum time (IDMT),
46IT Setting
sets the pick-up current level for the element.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC and ANSI curves using
46IT Char
. A time multiplier is applied to the characteristic curves using
the
46IT Time Mult
setting. Alternatively, a definite time lag delay (DTL) can be chosen using
46ITChar
. When
Delay (DTL) is selected the time multiplier is not applied and the
46IT Delay (DTL)
setting is used instead.
The
46IT Reset
setting can apply a,
definite time delayed
or
ANSI (DECAYING)
reset.
The 46DT element has a DTL characteristic.
46DT Setting
sets the pick-up current and
46DT Delay
the follower
time delay.
Operation of the negative phase sequence overcurrent elements can be inhibited from:
Inhibit 46IT
A binary or virtual input.
Inhibit 46DT
A binary or virtual input.
Figure 3.7-1 Logic Diagram: Negative Phase Sequence Overcurrent (46NPS)
©2010 Siemens Protection Devices Limited
Chapter 1 Page 31 of 70