7SR224 Argus Commissioning & Maintenance Guide
©2010 Siemens Protection Devices Limited
Chapter 6 Page 33 of 73
2.8
Restricted Earth fault (64H)
7SR224
46
BC
46
NPS
(x2)
37
(x2)
49
50
BF
51V
V
L1
(V
A
)
V
L2
(V
B
)
V
L3
(V
C
)
V
4
(V
X
)
I
L1
(I
A
)
81
HBL
2
37
(x2)
49
50
BF
51V
I
L2
(I
B
)
81
HBL
2
37
(x2)
49
50
BF
51V
I
L3
(I
C
)
81
HBL
2
60
CTS
60
VTS
I
4
(I
G
/I
SEF
)
74
TCS
(x3)
NOTE: The use of some
functions are mutually exclusive
67/
50
(x4)
67/
51
(x4)
67/
50
(x4)
67/
50
(x4)
67/
51
(x4)
67/
51
(x4)
64
H
27
59
27
59
(x4)
27
59
(x4)
27
59
(x4)
47
(x2)
79
59N
(x2)
Note:
Example shows
Voltage Config =
Van, Vbn, Vcn
81
(x4)
67/
50G
(x4)
67/
51G
(x4)
67/
50S
(x4)
67/
51S
(x4)
27S
59S
27S
59S
27S
59S
Batt
Test
Cap.
Test
Figure 2-9
Restricted Earth Fault
Voltage Inputs:
n/a
Current Inputs:
I
4
(I
REF
)
Disable:
51SEF, 50SEF, 79
Map Pickup LED:
64H - Self Reset
The setting resistance should be measured and the value compared to that specified in the settings data. Both
values should be recorded.
Settings Data Resistor Value
Measured
The high value of setting resistance R will often interfere with secondary current injection when using a digital test
set. It is normal practice in these cases to short out the resistor to allow testing, the shorting link should be
removed after testing.
Since the DTL setting is generally small the pick-up setting can be tested by gradually increasing current until
element operates. The relay should be disconnected from the current transformers for this test.
Apply 2x setting current if possible and record operating time