7SR224 Argus Performance Specification
4.2
Loss of Voltage (LOV) Loop Automation Function
4.2.1 Reference (LOV-A/X Dead/Live )
Parameter
Value
Live Vs
Setting
5, 5.5… 80V
Dead Vs
Setting
5, 5.5… 80V
4.2.2 Operate and Reset Level
Attribute
Value
V
op
Operate level
100 % Live
Vs
,
±
2 % or
±
0.5 V
Reset level
100 % Dead
Vs
,
±
2 % or
±
0.5 V
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
4.2.3 Reference LOV Automation Timers
Attribute
Value
t
op
LOV Primed Time
0, 1 … 600s
t
op
LOV Action Delay
0, 1 … 600s
t
op
LOV-A Action Delay
0, 1 … 600s
t
op
LOV-X Action Delay
0, 1 … 600s
t
op
LOV Sequence Time
0, 1 … 600s
t
op
LOV Reclose Delay
0, 1 … 600s
t
op
LOV SOTF Time
0, 1 … 600s
t
op
LOV Reclaim Time
0, 1 … 600s
t
op
LOV Memory Time
0, 1 … 600s
4.2.4 Operate Time LOV Automation Timers
Attribute
Value
t
op
Accuracy
t
op
,
±
1 % or
±
50ms
Repeatability
±
1 % or
±
50ms
©2010 Siemens Protection Devices Limited
Chapter 3 Page 49 of 49