7SR224 Argus Performance Specification
3.3
60CTS Current Transformer Supervision
3.3.1 Reference
Parameter
Value
I
thresh
Current Threshold
0.05, 0.1… 1 x
In
V
thresh
Voltage Threshold
7, 8… 110V
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
3.3.2 Current & Voltage Threshold
Attribute
Value
I
op
CT failed current level
100 %
I
thresh
,
±
5% or
±
1% In
Reset level
90 %
I
op,
±
5% or
±
1% In
V
op
CT failed voltage level
100 %
V
thresh
,
±
2% or
±
0.5V
Reset level
110 %
V
op
,
±
2 % or
±
0.5V
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
harmonics to
f
cutoff
≤
5 %
3.3.3 Operate and Reset Time
Attribute
Value
t
basic
Basic operate time
30 ms
±
20ms
Operate time
t
basic
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
©2010 Siemens Protection Devices Limited
Chapter 3 Page 43 of 49