7SR224 Argus Performance Specification
2.10 51G Time Delayed Measured Earth Fault
2.10.1 Reference
Parameter
Value
Is
Setting 0.005,
0.006
…0.100, 0.105… 1.0
xIn
Char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Manufacturer specific curves
See ‘Performance Specification Appendix 1’
Tm
Time Multiplier setting
0.025, 0.05… 1.6
t
d
Delay setting (DTL)
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s
IDMTL
2 to 20 x
Is
I
Applied current (for
operate time)
DTL 5
x
Is
2.10.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
105 %
Is
,
±
4 % or
±
1%
In
Reset level
≥
95 %
I
op
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
©2010 Siemens Protection Devices Limited
Chapter 3 Page 28 of 49