7SR224 Argus Performance Specification
2.16 81Under/Over Frequency
2.16.1 Reference
Parameter
Value
Fs
Setting
40, 40.01… 69.99 Hz
Hyst
Hysteresis setting
0, 0.1… 80%
td
Delay setting
0.00, 0.01… 20.0, 20.5… 100.0, 101.…1000, 1010 … 10000 ,
10100 … 14400 s
2.16.2 Operate and Reset Level
Attribute
Value
F
op
Operate level
100 %
F
s
,
±
10mHz
overfrequency
(100 % -
hyst
)
xF
op,
±
10mHz
Reset level
underfrequency
(100 % +
hyst
)
xF
op,
±
10mHz
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
2.16.3 Operate and Reset Time
Attribute
Value
Typically
<
110ms
overfrequency
Maximum
<
150ms
Typically
<
110ms
t
basic
Element basic
operate time
(for ROCOF
between 0.1
and 5.0 Hz/sec)
underfrequency
Maximum
<
150ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Disengaging time
<
100 ms
©2010 Siemens Protection Devices Limited
Chapter 3 Page 40 of 49