
7SR224 Argus Performance Specification
2.14 64H Restricted Earth Fault Protection
2.14.1 Reference
Parameter
Value
Is
Setting
0.005, 0.006 ..0.100, 0.105… 0.95 x
In
t
d
Delay setting
0.00, 0.01… 20.0, 20.1… 100.0, 101.…1000, 1010 …
10000 , 10100 … 14400 s
2.14.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
xIn
Reset level
95 %
I
op
,
±
5 % or
±
0.1%
xIn
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.14.3 Operate and Reset Time
Attribute
Value
0 to 2 x
Is
, 40 ms,
±
10ms
t
basic
Element basic operate time
0 to 5 xI
s
, 30 ms,
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1% or
±
10ms
Repeatability
±
1% or
±
10ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms
©2010 Siemens Protection Devices Limited
Chapter 3 Page 38 of 49