7SR224 Argus Settings, Configuration & Instruments
1.4 Instruments
Mode
The Instrument Mode sub-menu displays key quantities and information to aid with commissioning. The following
meters are available and are navigated around by using the READ UP
▲
, READ DOWN
▼
and TEST/REST
buttons.
NB: The Instruments Mode may vary between software versions. Please see the appendices to this section of the
manual for relevant software version.
1.5
Fault Data Mode
The Fault Data Mode sub menu lists the time and date of the previous ten protection operations. The stored data
about each fault can be viewed by pressing the TEST/RESET
►
button. Each record contains data on the
operated elements, analogue values and LED flag states at the time of the fault. The data is viewed by scrolling
down using the READ DOWN
▼
button.
1.6 Control
Mode
This mode provides convenient access to commonly used relay control and test functions. When any of the items
listed below are selected control is initiated by pressing the ENTER key. The TEST/RESET
►
button is used to
toggle between the available options. The user is prompted to confirm the action, again by pressing the ENTER
key, before the command is executed. If the action is not confirmed within a short time the action is automatically
cancelled.
Control Mode commands can be password protected by using the Control Password function
Commands available in the Control Mode are:
CB: Open or CB: Close
AR: In Service or AR: Out of Service
AR: Trip and Reclose
AR: Trip & Lockout
Hotline Working: In or Hotline Working: Out
E/F Protection: In or E/F Protection: Out
SEF Protection: In or SEF Protection: Out
Inst Protection: In or Inst Protection: Out
Battery Test
Set Local Mode
Set Local or Remote Mode
Set Remote Mode
Set Service Mode
©2010 Siemens Protection Devices Limited
Chapter 2 Page 8 of 13