7SR224 Argus Data Comms
Information Object Addresses (IOA)
The following table lists information object address (IOA) definitions together with a description of the message
and default function type of that message. Definitions with shaded area are not available on all relay models.
The Default type is given below but all items are user configurable.
IOA Description
Default
Type
1 Data Lost
M_SP_TB_1
4 Remote Mode
M_SP_TB_1
C_SC_NA_1
5 Service Mode
M_SP_TB_1
C_SC_NA_1
6 Local Mode
M_SP_TB_1
C_SC_NA_1
7 Local & Remote Mode
M_SP_TB_1
C_SC_NA_1
12 Control Received
M_SP_TB_1
13 Command Received
M_SP_TB_1
14 Cold Start
M_SP_TB_1
15 Warm Start
M_SP_TB_1
16 Re-start
M_SP_TB_1
17 Trigger Storage
M_SP_TB_1
18 Clear Waveform Records
M_SP_TB_1
19 Clear Fault Records
M_SP_TB_1
20 Clear Event Records
M_SP_TB_1
21 Reset Demand metering
M_SP_TB_1
C_SC_NA_1
22 27 Sag SARFI
M_SP_TB_1
23 59Swell SARFI
M_SP_TB_1
24 Reset SagSwell Count
M_SP_TB_1
25 Battery Test Pass
M_SP_TB_1
26 Battery Test Fail
M_SP_TB_1
27 Battery Ohms High
M_SP_TB_1
28 Battery Volts Low
M_SP_TB_1
29 Battery Volts High
M_SP_TB_1
30 Battery Healthy
M_SP_TB_1
31 Battery Recovery Fail
M_SP_TB_1
32 Battery Test
M_SP_TB_1
C_SC_NA_1
33 Capacitor Ready
M_SP_TB_1
34 Capacitor Test Pass
M_SP_TB_1
35 Capacitor Test Fail
M_SP_TB_1
36 Capacitor Recovery Fail
M_SP_TB_1
37 Capacitor Test
M_SP_TB_1
C_SC_NA_1
38 General Alarm 1
M_SP_TB_1
39 General Alarm 2
M_SP_TB_1
40 General Alarm 3
M_SP_TB_1
41 General Alarm 4
M_SP_TB_1
©2010 Siemens Protection Devices Limited