7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited
Chapter 4 Page 51 of 76
Binary Output Status Points
Static Object Number:
10
Change Event Object Number:
11
Default Variation reported when variation 0 requested:
2 (Binary Output with flags)
Default Change Event variation 0 requested:
2 (Binary Output absolute time)
Control Relay Output Blocks
Object Number:
12
All objects are default class 2
Point
Index
Name/Description
Supported Control Relay Output Block
Fields
72
Reset CB-A Delta Trip Count
Pulse On/Latch On
73
Reset CB-B Delta Trip Count
Pulse On/Latch On
74
Reset CB-C Delta Trip Count
Pulse On/Latch On
75
Reset CB-A Count To AR Block
Pulse On/Latch On
76
Reset CB-B Count To AR Block
Pulse On/Latch On
77
Reset CB-C Count To AR Block
Pulse On/Latch On
78
Reset CB-A Frequent Ops Count
Pulse On/Latch On
79
Reset CB-B Frequent Ops Count
Pulse On/Latch On
80
Reset CB-C Frequent Ops Count
Pulse On/Latch On
81
Reset CB-A LO Handle Ops Count
Pulse On/Latch On
82
Reset CB-B LO Handle Ops Count
Pulse On/Latch On
83
Reset CB-C LO Handle Ops Count
Pulse On/Latch On
84
Reset CB-A I^2t Wear
Pulse On/Latch On
85
Reset CB-B I^2t Wear
Pulse On/Latch On
86
Reset CB-C I^2t Wear
Pulse On/Latch On
87
Reset Energy Meters
Pulse On/Latch On
88
Remote Mode
Pulse On/Latch On
89
Service Mode
Pulse On/Latch On
90
Local Mode
Pulse On/Latch On
91
Local & Remote
Pulse On/Latch On
92
Man Override Sync on/off
Pulse On / Pulse Off / Latch On / Latch Off
93
79 Override Sync on/off
Pulse On / Pulse Off / Latch On / Latch Off