7SR224 Argus Settings, Configuration & Instruments
©2010 Siemens Protection Devices Limited
Chapter 2 Page 12 of 13
Setting name
Range
Default
Units
Notes
Station Address
1 – 254 for IEC60870-5-
103 or IEC60870-5-101
0 – 247 for Modbus RTU
0 – 65534 for DNP3.0
0
Address given to relay to
identify that relay from
others which may be using
the same path for
communication as other
relays for example in a fibre
optic hub
COM1-RS485 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
or IEC60870-5-101
IEC60870-5-
103
COM1 is the rear mounted
RS485 port
COM1-RS485 Baud
Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM1-RS485 Parity
NONE, ODD, EVEN
EVEN
COM2-USB Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, ASCII,
DNP3.0 or IEC60870-5-
101
IEC60870-5-
103
COM2 is the front USB port.
COM2-USB Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
230400 460800 921600
57600
COM2-USB Parity
NONE, ODD, EVEN
EVEN
COM3 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
or IEC60870-5-101
IEC6-0870-5-
103
COM3 This is an optional
rear mounted optional
connection
COM3 Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200
57600
COM3 Parity
NONE, ODD, EVEN
EVEN
COM3 Line Idle
LIGHT ON, LIGHT OFF LIGHT
OFF
COM3 Data echo
ON, OFF
OFF
COM4 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0
or IEC60870-5-101
OFF
COM4 This is an optional
rear mounted optional
connection
COM4 Baud Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM4 Parity
NONE, OFF, EVEN
EVEN
COM4 Line Idle
LIGHT ON, LIGHT OFF LIGHT
OFF
COM4 Data echo
ON, OFF
OFF
NB: The Data Communication Configuration may vary between software versions. Please see the appendices to
this section of the manual for relevant software version.