7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited
Chapter 4 Page 67 of 76
IOA Description
Default
Type
398 25 Close On Zero
M_SP_TB_1
399 25 System Split
M_SP_TB_1
400 25 Live Line
M_SP_TB_1
401 25 Live Bus
M_SP_TB_1
402 25 Line U/V
M_SP_TB_1
403 25 Bus U/V
M_SP_TB_1
404 25 Voltage Dif >
M_SP_TB_1
405 25 CS Slip Freq >
M_SP_TB_1
406 25 SS Slip Freq >
M_SP_TB_1
407 25 COZ Slip Freq >
M_SP_TB_1
408 25 In Sync
M_SP_TB_1
409 25 CS In Progress
M_SP_TB_1
410 25 SS In Progress
M_SP_TB_1
411 25 COZ In Progress
M_SP_TB_1
412 25 System Split LO
M_SP_TB_1
413 60VTF-Bus
M_SP_TB_1
415 Man Override Sync
M_SP_TB_1
416 79 Override Sync
M_SP_TB_1
417 Dead Line Close
M_SP_TB_1
418 Dead Bus Close
M_SP_TB_1
419 Wattmetric Po>
M_SP_TB_1
420 Close CB-A Failed
M_SP_TB_1
421 Open CB-A Failed
M_SP_TB_1
422 CB-A Reclaim
M_SP_TB_1
423 CB-A Lockout
M_SP_TB_1
424 CB-A Successful Close
M_SP_TB_1
425 CB-A Successful DAR Close
M_SP_TB_1
426 CB-A Successful Man Close
M_SP_TB_1
427 CB-A Total Trip Count
M_SP_TB_1
428 CB-A Delta Trip Count
M_SP_TB_1
429 CB-A Count To AR Block
M_SP_TB_1
430 Reset CB-A Total Trip Count
M_SP_TB_1
C_SC_NA_1
431 Reset CB-A Delta Trip Count
M_SP_TB_1
C_SC_NA_1
432 Reset CB-A Count to AR Block
M_SP_TB_1
C_SC_NA_1
433 CB-A I^2t Wear
M_SP_TB_1
434 Reset CB-A I^2t Wear
M_SP_TB_1
C_SC_NA_1
435 CB-A 79 AR In progress
M_SP_TB_1
436 CB-A Frequent Ops Count
M_SP_TB_1
437 Reset CB-A Frequent Ops Count
M_SP_TB_1
C_SC_NA_1
438 CB-A LO Handle Ops Count
M_SP_TB_1
439 Reset CB-A LO Handle Ops Count
M_SP_TB_1
C_SC_NA_1
440 PhA Inst Protection Inhibited
M_SP_TB_1
441 CB-A Blocked By Interlocking
M_SP_TB_1
442 CB-A on by auto reclose
M_SP_TB_1
443 CB-A Trip & Reclose
M_SP_TB_1
444 50BF-1 Pole A
M_SP_TB_1
445 50BF-2 Pole A
M_SP_TB_1