7SR224 Argus Performance Specification
1.4
Environmental Performance
1.4.1 General
1.4.1.1
Temperature
IEC 60068-2-1/2
Type Level
Operating range
-10
°
C to +55
°
C
Storage range
-25
°
C to +70
°
C
1.4.1.2
Humidity
IEC 60068-2-3
Type Level
Operational test
56 days at 40
°
C and 95 % relative humidity
1.4.1.3
Transient Overvoltage
IEC 60255-5
Type Level
Between all M4 terminals and earth, or
between any two independent circuits
5.0 kV, 1.2/50
μ
s 0.5j
1.4.1.4
Insulation
IEC 60255-5
Type Level
Between any M4 terminal and earth
Between independent circuits
2.5 kV AC RMS for 1 min
Across normally open contacts
1.0 kV AC RMS for 1 min
1.4.1.5
IP Ratings
Type Level
Installed with cover on
IP 50 from front
Installed with cover removed
IP 30 from front
1.4.2 Emissions
IEC 60255-25
1.4.2.1
Radiated Radio Frequency
Type
Limits at 10 m, Quasi-peak
30 to 230 MHz
40 dB(
μ
V/m)
230 to 10000 MHz
47 dB(
μ
V/m)
1.4.2.2
Conducted Radio Frequency
Limits
Type
Quasi-peak Average
0.15 to 0.5 MHz
79 dB(
μ
V) 66
dB(
μ
V)
0.5 to 30 MHz
73 dB(
μ
V) 60
dB(
μ
V)
©2010 Siemens Protection Devices Limited
Chapter 3 Page 13 of 49