7SR224 Argus Performance Specification
2.4
47 Negative Phase Sequence Voltage
2.4.1 Reference (47)
Parameter
Value
Vs
Setting
1, 1.5… 90V
Hyst.
Hysteresis
0, 0.1… 80%
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010… 10000,
10100… 14400 s
2.4.2 Operate and Reset Level (47)
Attribute
Value
V
op
Operate level
(100%-hyst) x
Vop
,
±
1 % or
±
0.25 V
Reset level
≥
95 %
V
op
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.4.3 Operate and Reset Time (47)
Attribute
Value
0V to 2
xVs
, 80 ms,
±
20ms
t
basic
Element basic operate time
0V to 10
xVs
, 55 ms,
±
20ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
2 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Overshoot time
< 40 ms
Disengaging time
< 60 ms
©2010 Siemens Protection Devices Limited
Chapter 3 Page 20 of 49