7SR224 Argus Performance Specification
3.5
60VTF-B
US
Voltage Transformer Supervision
3.5.1 Reference (60VTF)
Parameter
Value
t
d
Operate time
0.1, 0.2 … 100s
3.5.2 Operate and Reset Time
Attribute
Value
t
basic
Basic operate time
30 ms
±
20ms
Operate time
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
3.6
74TCS Trip Circuit Supervision
3.6.1 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
30ms
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
©2010 Siemens Protection Devices Limited
Chapter 3 Page 45 of 49