Fault table CiA402 profile
Operating Instructions – MOVIMOT
®
flexible
307
8.7.25
Fault 32 Communication
Subfault: 32.2
Description: EtherCAT
®
/SBus
PLUS
process data timeout
Response: Fieldbus – timeout response
Cause
Measure
Process data timeout during EtherCAT
®
/SBus
PLUS
communication.
– Check the wiring of the system bus and module
bus.
– Check for correct setting of the EtherCAT
®
/
SBus
PLUS
configuration in the MOVI-C
®
CONTROLLER.
– Check the EtherCAT
®
/SBus
PLUS
timeout setting
in the device.
Subfault: 32.3
Description: Faulty synchronization signal
Response: External synchronization
Cause
Measure
Faulty synchronization signal period.
Check for correct setting of the EtherCAT
®
/
SBus
PLUS
configuration in the MOVI-C
®
CONTROLLER.
Subfault: 32.4
Description: No synchronization signal
Response: External synchronization
Cause
Measure
No synchronization signal present.
Check for correct setting of the EtherCAT
®
/
SBus
PLUS
configuration in the MOVI-C
®
CONTROLLER.
Subfault: 32.5
Description: Synchronization timeout
Response: External synchronization
Cause
Measure
Timeout while synchronizing to synchronization
signal.
Check for correct setting of the EtherCAT
®
/
SBus
PLUS
configuration in the MOVI-C
®
CONTROLLER.
Subfault: 32.6
Description: Copy parameter set
Response: Output stage inhibit
Cause
Measure
Error while downloading parameter set to device.
– Check the wiring of the system bus and module
bus.
– Restart download.