Fault table standard
Operating Instructions – MOVIMOT
®
flexible
253
Subfault: 32.7
Description: Application heartbeat timeout
Response: Application heartbeat – timeout response
Cause
Measure
Communication interrupted between IEC program
in MOVI-C
®
CONTROLLER and device.
– Check the status of the IEC program.
– Restart the IEC program.
Subfault: 32.8
Description: User-timeout timeout
Response: User timeout timeout response
Cause
Measure
The timeout time of the user timeout function
elapsed.
Write the parameter for triggering the user
timeout function cyclically before the timeout time
elapses.
Subfault: 32.11
Description: Local mode timeout
Response: Local mode – timeout response
Cause
Measure
Communication connection to device interrupted
in local mode.
– Increase the timeout setting in local mode.
New Scope project created.
– Reset the fault.
– Restart local operation.
Scope measurement loaded from device.
– Reset the fault.
– Restart local operation.
Subfault: 32.12
Description: Manual mode timeout
Response: Manual mode – timeout response
Cause
Measure
Communication connection to device interrupted
in manual mode.
– Check whether too many programs are open on
the operator PC.
– Increase the timeout time in manual mode.
New Scope project created.
– Reset the fault.
– Restart manual mode.
Scope measurement loaded from device.
– Reset the fault.
– Restart manual mode.
29128668/EN – 12/2019