8
Service
Fault table standard
Operating Instructions – MOVIMOT
®
flexible
230
Subfault: 16.40
Description: Data of selected motor not valid
Response: Output stage inhibit
Cause
Measure
Startup data set on replaceable memory module
not valid for this motor.
Replace the memory module.
Subfault: 16.41
Description: Data of selected motor do not exist
Response: Output stage inhibit
Cause
Measure
No startup data set found on the replaceable
memory module for the selected motor.
Check the selection and, if necessary, start up
another motor or replace the memory module.
Subfault: 16.50
Description: Brake parameters not initialized
Response: Output stage inhibit
Cause
Measure
No brake data present
Check startup.
8.6.13
Fault 17 Internal processor fault
Subfault: 17.7
Description: Exception error
Response: Output stage inhibit
Cause
Measure
Exception trap in CPU.
Contact SEW-EURODRIVE Service.
8.6.14
Fault 18 Software errors
Subfault: 18.1
Description: Motor management
Response: Output stage inhibit
System state: Fault acknowledgement with CPU reset
Cause
Measure
Error detected at motor management interface.
– Switch the device off and on again.
– Contact the SEW‑EURODRIVE Service if the
error persists.
29128668/EN – 12/2019