18.27
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Synchrophasors
C37.118 Synchrophasor Protocol
➤
Station battery voltage
➤
No relay control from the PMU communications port, for the initial
stage of the project
The utility is able to meet the grid operator requirements with the relay, an
SEL-2600A RTD Module, an SEL-2407 Satellite-Synchronized Clock, and an
SEL-3373 Station Phasor Data Concentrator (PDC) in each substation.
This example will cover the PMU settings in one of the relays.
Some system details:
➤
The nominal frequency is 60 Hz.
➤
The line is protected by a breaker-and-a-half scheme.
➤
The station ambient temperature is collected by an SEL-2600A,
Channel RTD01.
➤
The line pts and wiring have a phase error of 4.20 degrees (lagging)
at 60 Hz.
➤
The Breaker 1 cts and wiring have a phase error of 3.50 degrees
(lagging) at 60 Hz.
➤
The Breaker 2 cts and wiring have a phase error of 5.50 degrees
(lagging) at 60 Hz.
➤
The synchrophasor data will be using Port 3, and the maximum bps
allowed is 19200.
➤
The system designer specified floating point numeric representation
for the synchrophasor data, and rectangular coordinates.
➤
The system designer specified integer numeric representation for the
frequency data.
➤
The system designer specified fast synchrophasor response, because
the data are being used for system monitoring.
The protection settings and RTD serial port settings will not be shown.
Determining Settings
The protection engineer performs a bandwidth check, using
, and
determines the required message size. The system requirements, in order of
appearance in
, are as follows.
➤
5 Synchrophasors, in floating point representation
➤
Integer representation for the frequency data
➤
2 analog values
➤
3 digital status bits, which require one status word
The message size is 16 + 5 • 8 + 2 • 2 + 2 • 4 + 1 • 2 = 70 bytes. Using
, the engineer verifies that the port bps of 19200 is adequate for the
message, at 10 messages per second.
Protection Math Variables PMV64 and PMV63 will be used to transmit the
RTD01 ambient temperature data and the station battery voltage DC1, respectively.
The Protection SEL
OGIC
Variables PSV64, PSV63, and PSV62 will be used to
transmit the breaker status, loss-of-potential alarm, and frequency measurement
status, respectively.
The Port 3 FASTOP setting will be set to N, to disable any control attempts from
the PMU port.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...