5.118
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Functions
Switch-Onto-Fault Logic
Circuit Breaker Closed SOTF Logic
You can detect circuit breaker close bus assertion by monitoring the dc close bus.
Connect a control input on the SEL-421 to the dc close bus. The control input
energizes whenever a manual close or automatic reclosure occurs. Set SEL
OGIC
control equation CLSMON (Close Signal Monitor) to monitor the control input
(e.g., CLSMON := IN102) and consequently detect close bus assertion.
Set ESOTF to Y and set CLOEND to other than OFF to enable the circuit
breaker-closed SOTF logic. The CLOEND timer operates when one or three
poles open (SPO or 3PO asserts). If the 3PO or SPO condition continues longer
than the CLOEND time and the close bus asserts (SEL
OGIC
control equation
CLSMON equals logical 1), Relay Word bit SOTFE asserts and remains asserted
for dropout time setting SOTFD or until the logic detects a healthy voltage condi-
tion (if EVRST := Y, see
).
SOTF Options
Set EVRST = Y to enable the Voltage Reset logic. If the system voltage is bal-
anced (ratio of negative-sequence voltage to positive-sequence voltage is below
0.1), Relay Word bit SOTFE resets when the relay measures positive-sequence
voltage at greater than VRSTPU times nominal voltage.
If setting ESPSTF (Single-Pole SOTF Enable) is enabled (ESPSTF := Y), the
relay provides SOTF protection for an SPO condition.
Table 5.67
SOTF Settings
Setting
Prompt
Range
Default
(5 A)
ESOTF
Switch-Onto-Fault
Y, N
Y
ESPSTF
Single-Pole Switch-Onto-Fault
Y, N
N
EVRST
Switch-Onto-Fault Voltage Reset
Y, N
N
VRSTPU
Switch-Onto-Fault Reset Voltage (0.60–1.00 Pu) 0.60–1.00 pu
0.8
52AEND
52a Pole Open Time Delay (cycles)
OFF, 0.000–16000
10.000
CLOEND
CLSMON or Single Pole Open Delay (cycles)
OFF, 0.000–16000
OFF
SOTFD
Switch-Onto-Fault Enable Duration (cycles)
0.500–16000
10.000
CLSMON
Close Signal Monitor
SEL
OGIC
Equation NA
Table 5.68
SOTF Relay Word Bits
Name
Description
SOTFE
Switch-Onto-Fault Trip Logic Enabled
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...