8.18
SEL-421 Relay
Instruction Manual
Date Code 20171021
Settings
Group Settings
Make
settings when Group setting E21MG := 1–5 or E21XG := 1–5.
The number of pickup settings in
is dependent on Group settings
E21G := 1–5 and E21XG := 1–5, and the settings made from
and
NOTE:
If the relay is using a remote
data acquisition system, such as TiDL,
the operating times will be delayed by
1.5 ms. Use caution when setting the
relay coordination times to account
for this added delay.
Make
settings when Group setting ESERCMP := Y.
NOTE:
The SEL-421-4 does not
provide series-compensated line
protection logic. This setting is
available in the SEL-421-5.
Make
settings only when Group setting ECDTD := Y; the number of
settings is dependent on Group settings E21P := 1–5, E21G := 1–5, and
E21XG := 1–5, and the settings made from
and
Table 8.42
Zero-Sequence Compensation Factor
Setting
Prompt
Default
Value
Increment
k0M1
Zone 1 Zero-Sequence Compensation Factor Magnitude
(AUTO, 0.000–10)
0.726
0.001
k0A1
Zone 1 Zero-Sequence Compensation Factor Angle
(–180.0 to +180.0 degrees)
–3.69
0.01
k0M
a
a
Setting only available when Group setting EADVS := Y.
Forward Zones Zero-Sequence Compensation Factor
Magnitude (0.000–10)
0.726
0.001
k0A
Forward Zones Zero-Sequence Compensation Factor
Angle (–180.0 to +180.0 degrees)
–3.69
0.01
k0MR
Reverse Zones Zero-Sequence Compensation Factor
Magnitude (0.000–10)
0.726
0.001
k0AR
Reverse Zones Zero-Sequence Compensation Factor
Angle (–180.0 to +180.0 degrees)
–3.69
0.01
Table 8.43
Ground-Distance Element Time Delay
Setting
Prompt
Default
Value
Increment
Z1GD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
0.000
0.125
Z2GD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
20.000
0.125
Z3GD
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
60.000
0.125
Z4GD
Zone 4 Time Delay (OFF, 0.000–16000 cycles)
OFF
0.125
Z5GD
Zone 5 Time Delay (OFF, 0.000–16000 cycles)
OFF
0.125
Table 8.44
Series Compensation
Setting
Prompt
Default Value
Increment
5 A
1 A
XC
Series Capacitor Reactance
(OFF, 0.05–64
secondary) 5 A
(OFF, 0.25–320
secondary) 1 A
OFF
OFF
0.01
Table 8.45
Distance Element Common Time Delay (Sheet 1 of 2)
Setting
Prompt
Default
Value
Increment
Z1D
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
0.000
0.125
Z2D
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
20.000
0.125
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...